Message Overview:
Message Description:
Automatic pressurization modes have failed or no data is being received from the outflow valve to the IASCs and the system is not in manual mode.
Possible Causes:
- Outflow Valve (OFV) (MPE1)
- Integrated Air System Controller 1 - FWD (IASC 1) (A55)
- Integrated Air System Controller 2 - AFT (IASC 2) (A56)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-21-0047 - No MDC Report upon "AUTO PRESS FAIL" CAS Message
Forum Articles/Infoservice/Newsletter: None
IASC LOGIC:
- The IASC is looking for data from the outflow valve.
- The IASC received OFV Auto Channel INOP from the OFV.
Quick Links:
| Operational Test of the Cabin Pressure Control System | AMM 21-31-00-710-801 |
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Operational Test of the Integrated Air System (IAS) Controller | AMM 21-31-01-710-801 |
| Removal of the Outflow Valve | AMM 21-31-05-000-801 |
| Installation of the Outflow Valve | AMM 21-31-05-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Check the current faults and fault history for problems related to the IASC controller and pressurization system.
- If the 'AUTO PRESS FAIL' CAS message is displayed and there are no message recorded in the MDC, continue with next step.
- Perform the Operational Test of the Cabin Pressure Control System.
- If test passes, do close out.
- If test fails, continue with the next step.
- Replace Outflow Valve.
- Do close out.