Message Overview:
Message Description:
Oil temperature greater than 325°F. For ground operation, this failure triggers a protective shut-down. For flight operation, the shut-down is inhibited.
- The ESU has determined that the sensed oil temperature from the oil temperature transducer is out of specifications.
Possible Causes:
- APU Oil Temp Sensor (RT01)
- APU Oil Temp Sensor Connector
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Quantity Check of the Oil Supply in the APU | AMM 12-14-09-610-801 |
| Servicing of the APU Oil Supply | AMM 12-14-09-612-801 |
| Draining of the APU Oil System | AMM 49-91-00-680-801 |
| Removal of the Low Oil-Pressure Switch | AMM 49-91-17-000-801 |
| Installation of the Low Oil-Pressure Switch | AMM 49-91-17-400-801 |
Troubleshooting Recommendations:
- Verify oil system servicing. If the oil is close to 800 hours, drain, and service.
- Check the oil temperature sensor resistance by ringing from A39AP1 pins 4C to 4D, compare reading and cross check against oil temperature using the following table:
°C Resistance °C Resistance -70 68.27 ± 0.50 60 112.28 ± 0.50 -60 71.19 ± 0.50 70 116.27 ± 0.50 -50 74.24 ± 0.40 80 120.36 ± 0.50 -40 77.39 ± 0.40 90 124.55 ± 0.50 -30 80.56 ± 0.40 100 128.85 ± 0.50 -20 83.77 ± 0.40 110 133.26 ± 0.50 -10 87.04 ± 0.40 120 137.78 ± 0.60 0 90.38 ± 0.40 130 142.40 ± 0.60 10 93.80 ± 0.40 140 147.11 ± 0.60 20 97.31 ± 0.40 150 151.91 ± 0.60 30 100.91 ± 0.40 200 177.95 ± 1.00 40 104.60 ± 0.40 250 208.00 ± 1.00 50 108.39 ± 0.40 300 242.70 ± 1.5 - If the sensor is out of limits from the table, check and repair wiring/remove and replace RT01.