Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

11/04/24

Message Overview:

Message Name:

INPUT Fault

Message Code:

B3-681726

Associated CAS:

AT FAIL
(Advisory)

Reporting LRU: Auto Throttle (AT) Computer
Effectivity: Post SB350-22-002
Aircraft 20937 and Subs
System Description: 22-30-00
Schematic Diagram: 22-30-00-801 - Auto Throttle System
31-45-00-101 - Integrated-Avionics Processor System (IAPS)
Wiring Diagram: 22-30-00-801 - Auto Throttle System (ATS)

Message Description:

Required input for AT function reported absent by the AT computer and IOC appears to be transmitting data.

Possible Causes:

  • Input Missing - Refer to Troubleshooting Recommendations for a list of possible inputs.
  • Autothrottle Computer (AT) (A252)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

NOTE: Review the Auto Throttle "AT Diagnostic Information", to find details about the MDC Data Reader Labels & bits.
NOTE: The Auto Throttle uses the same FGS, IRS, and ADS inputs as the transfer side Flight Director. Transferring the side of the Flight Guidance (XFR) will cause the Auto Throttle to switch input sides. In the event of a failure or erroneous data, although the Auto Throttle would initially disengage and report  "AT FAIL" Advisory CAS, an alternative Flight Director source of data may be selected using the Reversion Control Panel. If the reselected inputs are sufficient, the Auto Throttle can be re-engaged.
Other inputs (FADEC, Flaps, SPC, Radio Altitude) have other reversion capabilities, but these functions are automatic and not controlled by the crew. 

Quick Links:

Removal of the Auto Throttle Computer AMM 22-30-01-000-801
Installation of the Auto Throttle Computer AMM 22-30-01-400-801
Removal of the Input/Output Concentrator Unit (IOC) AMM 31-45-05-000-801
Installation of the Input/Output Concentrator Unit (IOC) AMM 31-45-05-400-801
Operational Test of the Input/Output Concentrator Unit (IOC) AMM 31-45-05-710-801
Removal of the Integrated-Avionics Processor System (IAPS) Card Cage (ICC) AMM 31-45-01-000-801
Installation of the Integrated-Avionics Processor System (IAPS) Card Cage (ICC) AMM 31-45-01-400-801
Operational Test of the Integrated-Avionics Processor System (IAPS) AMM 31-45-00-710-801
Safety Precautions - Maintenance Practices - ALL SPM 20-00-01-02-01
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02
Electrical Connectors - Maintenance Practice - ALL SPM 20-20-00-02-01

Troubleshooting Recommendations:

  1. Review the NOTES found in the Troubleshooting Tips element prior to starting this troubleshooting.
  2. On the Cursor Control Panel press “A/ICE”, “ECS”, “FUEL” buttons simultaneously, access the MDC on MFD #2.
  3. Highlight “LRU INDEX/OPERATIONS” then press “ENTER” button.
  4. Highlight “AT COMPUTER” then press the “ENTER” button.
  5. Press the “SKIP” button.
  6. Highlight Label “352” then press the “ENTER” button.
  7. View and record label 352 data.
  8. Compare the data recorded with the table below to identify what AT computer input is missing.

    LABEL BIT FIELD NAME FIELD DESCRIPTION
    352 11 L PFD Input Fault 0 = False / 1 = True
    352 12 L SPC Input Fault 0 = False / 1 = True
    352 13  L DCU Input Fault 0 = False / 1 = True
    352 14 L RA Input Fault 0 = False / 1 = True
    352 15 L ADC Input Fault 0 = False / 1 = True
    352 16 L IRS Input Fault 0 = False / 1 = True
    352 17 LA FADEC Input Fault 0 = False / 1 = True
    352 18 LB FADEC Input Fault 0 = False / 1 = True
    352 19 L IOC Input Fault 0 = False / 1 = True
    352 20 R PFD Input Fault 0 = False / 1 = True
    352 21 R SPC Input Fault 0 = False / 1 = True
    352 22 R DCU Input Fault 0 = False / 1 = True
    352 23 R RA Input Fault 0 = False / 1 = True
    352 24 R ADC Input Fault 0 = False / 1 = True
    352 25 R IRS Input Fault 0 = False / 1 = True
    352 26 RA FADEC Input Fault 0 = False / 1 = True
    352 27 RB FADEC Input Fault 0 = False / 1 = True
    352 28 R IOC Input Fault 0 = False / 1 = True
    352 29 Spare

  9. Use the MDC to view fault messages associated to system(s) identified in the previous step. Refer to SmartFix Plus troubleshooting procedures.
  10. Make sure the associated LRUs are powered and no communication faults are present.
  11. Do close out.