02/25/21
Message Overview:
Message Description:
The Pilot Initiated Test signal from PIT switch is asserted continuously for greater than 45 seconds.
Possible Causes:
- Fire-Detection-and-Extinguishing (FIREX) Control-Unit (A91)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-000-801 |
| Installation of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Assure that the test switch has not been pressed for more than 45 seconds.
- Verify the wiring from the press to test switch to the FIREX Control Unit (A91), plug A91P2, pin 34 should provide a ground when the press to test switch is pressed. Should be less than 1Ω.
- If resistance is higher than normal, suspect the S101 test reset switch, ground GS2442 (other components should be failed), or the wiring between the switch and FIREX control unit.
- If the wiring checks good, verify that the DCU is also receiving the press to test switch input. When the switch is pressed, A14EP1 should also receive a ground on pin 15H. Should be less than 1Ω. If the DCU is not receiving the ground, verify the wiring between the switch, ground GS2442, or S101 test reset switch.
- If the above discrete wiring checks good, swap out or replace the FIREX Control Unit.