Message Overview:
Message Description:
The Data Concentrator Unit and RDC does not receive any data from the channel A of the Integrated Air System Controller 1.
Possible Causes:
- Integrated Air System Controller (IASC1) (A55)
- Data Concentrator Unit (DCU) (A14)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Operational Test of the Integrated Air System (IAS) Controller | AMM 21-31-01-710-801 |
| Removal of the Data Concentrator Unit (DCU) | AMM 31-41-01-000-802 |
| Installation of the Data Concentrator Unit (DCU) | AMM 31-41-01-400-802 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Wire Repair | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Check the #1 IAS Controller circuit breaker CB1 D14 & CB1 E10, reset and re-check MDC for the bus fault.
- Check the #1 IAS Controller 28 VDC power input from CB1 D14 plug A55P2 pins 1 & 2. Verify the IAS controller channel A grounds A55P2 pins 3 & 4.
- Check the wiring between the #1 Integrated Air System Controller and the Data Concentrator Unit. IASC-A ARINC bus.
- Suspect the #1 IAS Controller, remove and replace per AMM.
- Operational test IAW AMM.