Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

08/09/21

Message Overview:

Message Name:

NO IASC2A BUS TO DCU-RDC

Message Code:

B3-384505

Associated CAS:

None

Reporting LRU: IASC2 TST A
System Description: 21-23-00
Schematic Diagram: 21-23-00
Wiring Diagram: 21-31-03

Message Description:

The Data Concentrator Unit does not receive any data from the channel A of the Integrated Air System Controller 2.

Possible Causes:

  • Integrated Air System Controller (IASC2) (A56)
  • Data Concentrator Unit (DCU) (A14)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

Quick Links:

Removal of the Integrated Air System (IAS) Controller AMM 21-31-01-000-801
Installation of the Integrated Air System (IAS) Controller AMM 21-31-01-400-801
Operational Test of the Integrated Air System (IAS) Controller AMM 21-31-01-710-801
Removal of the Data Concentrator Unit (DCU) AMM 31-41-01-000-802
Installation of the Data Concentrator Unit (DCU) AMM 31-41-01-400-802
Standard Practices - Replace Wiring SPM 20-12-00-02
Standard Practices - Wire Repair SPM 20-12-10-02

Troubleshooting Recommendations:

  1. Check the #2 IAS Controller circuit breaker CB2 D14 & CB2 E10, reset and re-check MDC for the bus fault.
  2. The #1 & #2 IASC A bus go from the IASCs to the DCU. The DCU then completes the data circulation on A-DCU-4, and B-DCU-4 buses. Check both A, and B-DCU-4 bus wiring into #1 IASC.
  3. Suspect the #2 IAS Controller, remove and replace per AMM.
  4. Operational test IAW AMM.