02/16/21
Message Overview:
Message Description:
R-IOC-4 data absent at SVC and RIU 1, while it is not reported failed by R-FMC or L-FMC.
Possible Causes:
- Config. Connector J2000
- Synthetic Vision Computer (SVC) (A230)
- Left Radio Interface Unit (RIU 1) (A17)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Radio Interface Unit (RIU) | AMM 23-51-21-000-801 |
| Installation of the Radio Interface Unit (RIU) | AMM 23-51-21-400-801 |
| Removal of the Synthetic Vision Computer (SVC) | AMM 34-34-01-000-801 |
| Installation of the Synthetic Vision Computer (SVC) | AMM 34-34-01-400-801 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Wire Repair | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset R IAPS (CB2-B6) circuit breaker.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do a wiring check of the ARINC 429 data bus R-IOC-4 from IAPS connector A4P103, through Config Connector J2000, to RIU 1 connector A17P2 and to SVC connector A230AP1. Repair/replace as required.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Replace SVC.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Replace RUI 1.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Do close out.