02/24/21
Message Overview:
Message Description:
L-IOC 4 (FMC) Input to DATALINK inactive and FMS is active to IOC and SVC.
Possible Causes:
- Left Radio Interface Unit (RIU) 1 (A17)
- Junction Box 4 (JB4)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Radio Interface Unit (RIU) | AMM 23-51-21-000-801 |
| Installation of the Radio Interface Unit (RIU) | AMM 23-51-21-400-801 |
| Removal of the Junction Boxes | AMM 24-63-01-000-802 |
| Installation of the Junction Boxes | AMM 24-63-01-400-802 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Wire Repair | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset RIU 1A (CB1-B5) and RIU 1B (CB1-B4) circuit breakers.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check of ARINC 429 data bus L-IOC-4 from RIU1 connector A17P2, through Junction Box 4 to IAPS connector A4P1. Repair/replace as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace RIU 1.
- Do close out.