Message Overview:
Message Description:
FIRE Extinguishing A power has failed. The CB2-A11 circuit breaker is open, wire is open, or FIREX Control Unit has failed.
Possible Causes:
- Missing 28 VDC input or ground to FIREX CU
- Fire-Detection-and-Extinguishing Control Unit (FIREX CU) (A91)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-000-801 |
| Installation of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset FIREX Control Unit (A91) circuit breakers CB2-A11. Check MDC for fault.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Measure for 28 VDC at 91P2 pin 1. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Measure for GND signal at 91P2 pins 9, 15, and 63. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace FIREX control unit.
- Do close out.