02/25/21
Message Overview:
Message Description:
Fault in FIREX Control Unit (CU) Bottle 1 discretes output to Data Concentrator Unit (DCU) is detected.
Possible Causes:
Possible Causes:
- Fire-Detection-and-Extinguishing Control Unit (FIREX CU) (A91)
- Data Concentrator Unit (DCU) (A14)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-000-801 |
| Installation of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-400-801 |
| Removal of the Data Concentrator Unit (DCU) | AMM 31-41-01-000-802 |
| Installation of the Data Concentrator Unit (DCU) | AMM 31-41-01-400-802 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Perform wiring check (short circuit to ground) between FIREX control unit (A91P1 pin 19, A91P1 pin 6, and A91P2 pin 19) and DCU (A14BP1 pin 9E, A14BP1 pin 8E, and A14BP1 10E) (repair as required).
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace FIREX control unit.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace DCU.
- Do close out.