Message Overview:
Message Description:
Fault in FIREX Control Unit (CU) SMOKE discrete output to Data Concentrator Unit (DCU) is detected.
Possible Causes:
- FIREX Control Unit (A91)
- Data Concentrator Unit (DCU) (A14)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-000-801 |
| Installation of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-400-801 |
| Removal of the Data Concentrator Unit (DCU) | AMM 31-41-01-000-802 |
| Installation of the Data Concentrator Unit (DCU) | AMM 31-41-01-400-802 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Perform wiring check (short circuit to ground) between FIREX control unit (A91P1 pin 21) and DCU (A14EP1 pin 15J) (repair as required).
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace FIREX control unit.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace DCU.
- Do close out.