Message Overview:
Message Description:
Data Concentrator Unit (DCU) is reporting an internal failure with channel A.
Possible Causes:
- Data Concentrator Unit (DCU) (A14)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Data Concentrator Unit (DCU) | AMM 31-41-01-000-802 |
| Installation of the Data Concentrator Unit (DCU) | AMM 31-41-01-400-802 |
Troubleshooting Recommendations:
- Reset EICAS DCU A Circuit Breaker CB1-D1 and EICAS DCU B Circuit Breaker CB2-D1. Is the fault message still present?
- If NO, do close out.
- If YES, continue with next step.
- Replace DCU (A14).
- Do close out.