Message Overview:
Message Description:
The OUTFLOW VALVE does not send any RS422 data to both IASCs.
Possible Causes:
- Junction Box 2 (JB2)
- Cabin Pressure Control System Outflow Valve (MPE1)
- Integrated Air System Controller (IASC) (A56)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-21-0047 - No MDC Report upon "AUTO PRESS FAIL" CAS Message (20003 - 20500)
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Operational Test of the Cabin Pressure Control System | AMM 21-31-00-710-801 |
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Operational Test of the Integrated Air System (IAS) Controller | AMM 21-31-01-710-801 |
| Removal of the Outflow Valve | AMM 21-31-05-000-801 |
| Installation of the Outflow Valve | AMM 21-31-05-400-801 |
| Removal of the Junction Box JB2 | AMM 24-63-05-000-803 |
| Installation of the Junction Box JB2 | AMM 24-63-05-400-803 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Wire Repair | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset Outflow Valve circuit breakers CB3-D6 and CB4-D6.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring checks from the Outflow Valve to the IASCs. Repair as required.
- If wiring checks passes, go to step 4.
- If wiring checks fails, continue with next step.
NOTE: Dual transmit and receive signals from the IAS Controllers and the outflow enable signal pass through Junction Box #2.
- Replace Junction Box #2.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Confirm proper operation of the Outflow Valve by doing the Section (2) of the Operational Test of the Cabin Pressure Control System.
- If test passes, do close out.
- If test fails, continue with next step.
- Replace Outflow Valve.
- Do close out.