02/03/21
Message Overview:
Message Description:
The right Input/Output Concentrator #2 (IOC 2) data bus inputs from the flight guidance computer #2 (FGC 2) are inactive.
Possible Causes:
- Right Flight Guidance Computer (FGC) 2 (A4-FGC)
- Right Input/Output Concentrator Unit (IOC) 2 (A4-IOC)
- Right Integrated-Avionics Processor System (IAPS) Power Supply (PWR 2) (A4-PWR)
- Integrated-Avionics Processor System (IAPS) Card Cage (ICC) (A4)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of Flight Guidance Computer (FGC) | AMM 22-11-01-000-801 |
| Installation of Flight Guidance Computer (FGC) | AMM 22-11-01-400-801 |
| Removal of Integrated Avionics Processor System (IAPS) Card Cage (ICC) | AMM 31-45-01-000-801 |
| Installation of Integrated Avionics Processor System (IAPS) Card Cage (ICC) | AMM 31-45-01-400-801 |
| Removal of Input/Output Concentrator Unit (IOC) | AMM 31-45-05-000-801 |
| Installation of Input/Output Concentrator Unit (IOC) | AMM 31-45-05-400-801 |
| Removal of the Integrated Avionics Processor System (IAPS) Power Supply (PWR) | AMM 31-45-09-000-801 |
| Installation of the Integrated Avionics Processor System (IAPS) Power Supply (PWR) | AMM 31-45-09-400-801 |
Troubleshooting Recommendations:
- Reset R IAPS Circuit Breaker CB2-B6. Is the fault message still present?
- If YES, continue with next step.
- If NO, do close out.
NOTE: Before you open the IAPS circuit breakers, make sure that all Engine FADEC circuit breakers are open. If the Engine FADEC circuit breakers remain closed, Engine Igniters will activate. This can cause injury to persons and damage to equipment.
- Swap Right FGC with Left FGC. Is the fault message still present?
- If YES, continue with next step.
- If NO, replace defective FGC.
- Swap Right IOC with Left IOC. Is the fault message still present?
- If YES, continue with next step.
- If NO, replace defective IOC.
- Swap IAPS PWR 2 with IAPS PWR 1. Is the fault message still present?
- If YES, continue with next step.
- If NO, replace defective IAPS PWR.
- Replace IAPS card cage (A4).
- Do close out.