Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

02/25/21

Message Overview:

Message Name:

HYD GEN CNTOR TEST FAIL
(Service Message)

Message Code:

B3-345656

Associated CAS:

None

Reporting LRU: HYD GEN CNTOR
System Description: 24-33-00
Schematic Diagram: 24-33-00
Wiring Diagram: 24-33-01
24-33-03

Message Description:

The HMDG Line Contactor, located inside the HMDG Power Center, has failed during Maintenance Test.

Possible Causes:

  • Hydraulic-Motor Driven Generator Power Center (HMDGPC) (A205)
  • Generator Control Unit (GCU) - Emergency (HMDGCU) (A206)
  • Remote Date Concentrator (RDC) (A13)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin:

  • SB100-24-04 - MODIFICATION - EMERGENCY DC-POWER SYSTEM - Installation of the Hydraulic Motor Driven Generator (HMDG) Option (C24-300)

Forum Articles/Infoservice/Newsletter: None

Fault Confirmation Procedure:
  • Retry, via the Forward Maintenance Panel, by setting the Maintenance Test Switch at the HYD GEN position and pushing / holding it for at least 5 seconds.
  • Monitor the MDC Current Service Message page.

Quick Links:

Removal of the Generator Control Unit (GCU) - Emergency AMM 24-33-09-000-801
Installation of the Generator Control Unit (GCU) - Emergency AMM 24-33-09-400-801
Removal of the Power Center AMM 24-33-13-000-801
Installation of the Power Center AMM 24-33-13-400-801
Removal of the Remote Data Concentrator (RDC) AMM 31-41-05-000-802
Installation of the Remote Data Concentrator (RDC) AMM 31-41-05-400-802
Standard Practices - Replace Wiring SPM 20-12-00-02
Standard Practices - Wire Repair SPM 20-12-10-02

Troubleshooting Recommendations:

  1. Do a wiring check of the following wires:

    From To Results
    RDC connector A13FP1 - pin G7 HMDGPC connector A205P1 - pin B
    Aircraft Ground Stud GS4214 HMDGPC connector A205P1 - pin A
    HMDG GCU connector A206P1 - pin M HMDGPC connector A205P1 - pin J
    HMDG GCU connector A206P1 - pin L HMDGPC connector A205P1 - pin K

    1. If wiring check is satisfying, go to next step.
    2. If wiring check is not satisfying, repair defective wire.

  2. Replace the HMDG Power Center (A205). Is the fault message still present?

    1. If YES, continue with next step.
    2. If NO, do close out.

  3. Replace the Generator Control Unit (GCU) - Emergency (A206). Is the fault message still present?

    1. If YES, continue with next step.
    2. If NO, do close out.

  4. Replace the Remote Data Concentrator (A13).
  5. Do close out.