Message Overview:
Message Description:
Absence of Stall Protection Computer (SPC) input to Data Concentrator Unit (DCU) and Input/Output Concentrator Unit (IOC).
Possible Causes:
- Stall Protection Computer (SPC) (A178)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-27-0105 - "STALL PROTECT FAIL" Nuisance CAS Message (20501 to 20999)
- SB100-27-14 - Modification - Stall Protection System - Introduction of the Stall Protection Computer (SPC) Part No. 822-1792-003 to Correct Loopback ARINC 429 Failure Messages (20501 - 20999)
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Operational Test of the Stall Protection System (SPS) | AMM 27-32-00-710-801 |
| Removal of the Stall Protection Computer | AMM 27-32-01-000-801 |
| Installation of the Stall Protection Computer | AMM 27-32-01-400-801 |
| Operational Test of the Integrated-Avionics Processor System (IAPS) | AMM 31-45-00-710-801 |
| Removal of the Integrated-Avionics Processor System (IAPS) Card Cage (ICC) | AMM 31-45-01-000-801 |
| Installation of the Integrated-Avionics Processor System (IAPS) Card Cage (ICC) | AMM 31-45-01-400-801 |
| Removal of the Input/Output Concentrator Unit (IOC) | AMM 31-45-05-000-801 |
| Installation of the Input/Output Concentrator Unit (IOC) | AMM 31-45-05-400-801 |
| Operational Test of the Input/Output Concentrator Unit (IOC) | AMM 31-45-05-710-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset the following circuit breakers and perform the Pilot Activated Test (PAT) of the Stall Protection System on the Systems Test control-panel located on the center pedestal.
- If system checks are good, do close out.
- If fault remains, continue with next step.
STALL L PWR CB1-B10 STALL R PWR CB2-B10 - Re-rack SPC and at the same time inspect connectors A178AP1 and A178BP1. Replace/repair as required.
- If system checks are good, do close out.
- If fault remains, continue to next step.
- Ensure 'main' power and ground are available at SPC channel A.
- If 28 VDC and ground are available at SPC connector A178AP1, go to step 5.
- If 28 VDC and ground are not available at SPC connector A178AP1, continue with next step.
- Do wiring check between SPC connectors A178AP1 and circuit breaker CB1-B10. Repair/replace as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Ensure "main" power and ground are available at SPC channel B.
- If 28 VDC and ground are available at SPC connector A178BP1, go to step 7.
- If 28 VDC and ground are not available at SPC connector A178BP1, continue with next step.
- Do wiring check between SPC connector A178BP1 and circuit breaker CB1-B11. Repair/replace as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace SPC.
- Do close out.