03/10/21
Message Overview:
Message Description:
B-LDU-1 bus is reported inoperative by Data Concentrator Unit (DCU) channel A and Data Concentrator Unit (DCU) channel B.
Possible Causes:
- Lamp Driver Unit (LDU) (A52)
- Data Concentrator Unit (DCU) (A14)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Data Concentrator Unit (DCU) | AMM 31-41-01-000-802 |
| Installation of the Data Concentrator Unit (DCU) | AMM 31-41-01-400-802 |
| Removal of the Lamp Driver Unit | AMM 31-52-01-000-801 |
| Installationof the Lamp Driver Unit | AMM 31-52-01-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset ANNUNCIATOR CTRL 2 Circuit Breaker CB2-D3, EICAS DCU A Circuit Breaker CB1-D1 and EICAS DCU B Circuit Breaker CB2-D1. Is the fault message still present?
- If NO, do close out.
- If YES, continue with next step.
- Do wiring check between DCU (A14) and LDU (A52) for the following wires:
From To Result Notes Conn. A14EP1 - 2A Conn. A52P2 - 69 1 Conn. A14EP1 - 2B Conn. A52P2 - 70 1 - If the check is satisfactory, continue with next step.
- If the check is not satisfactory, repair defective wiring.
NOTE 1: For A/C 20001 to 20124 Post IFIS STC ST01732LA-D or A/C 20003 to 20124 Post SB 100-46-06, there is a harness extension for the LDU, therefore the wiring check must done up to connector A52BP2.
- Replace LDU (A52). Is the fault message is still present?
- If NO, do close out.
- If YES, continue with next step.
- Replace DCU (A14).
- Do close out.