Message Overview:
Message Description:
PSEU Discrete Output DOT07A, MLGWOW to Left DC Power Center (A35) driver failed.
Possible Causes:
- Proximity-Sensor Electronic Unit (PSEU) (A9)
- DC Power Center (DCPC) (LH) (A35)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
MLGWOW (07A) MLGWOW (07B) GND/OPEN discrete WOWA is input to LDCPC. WOWB is input to RDCPC. Battery power is connected to all busses on WOW, but in flight connected to ESS bus only. Also, in case of only one generator operating in flight, power shared via shed busses. These are shown on EICAS synoptic page and no caution message issued for the loss of shed bus in flight.
PSEU discrete block diagram
Quick Links:
| Removal of the DC Power Center (DCPC) | AMM 24-61-01-000-801 |
| Installation of the DC Power Center (DCPC) | AMM 24-61-01-400-801 |
| Removal of the Proximity-Sensor Electronic Unit (PSEU) | AMM 32-61-09-000-801 |
| Installation of the Proximity-Sensor Electronic Unit (PSEU) | AMM 32-61-09-400-801 |
| Functional Test of the Proximity-Sensor Electronic Unit (PSEU) | AMM 32-61-09-720-801 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Wire Repair | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Pull and reset the PSEU gear system breakers (CB1-C13, CB1-C14, CB2-C13, CB2-C14).
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between LDCPC A35P2 pin u and PSEU A9CP1 pin 9D. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace PSEU.
- Do close out.