04/01/21
Message Overview:
Message Description:
If SB100-23-22, SATCOM/FANS installation, is incorporated: SVC and SDU are reporting failed L-IRS-4 bus input.
If SB100-23-22, SATCOM/FANS installation, is not incorporated: SVC is reporting a failed L-IRS-4 bus input.
Possible Causes:
- Inertial Reference Unit (IRU) No. 1 (A233)
- Junction Box (JB1)
- Synthetic Vision Computer (SVC) (A230)
- Satellite Data Unit (SDU) (A82)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the SATCOM Satellite Data Unit (SDU) | AMM 23-15-01-000-801 |
| Installation of the SATCOM Satellite Data Unit (SDU) | AMM 23-15-01-400-801 |
| Removal of the Junction Box JB1 | AMM 24-63-01-000-802 |
| Installation of the Junction Box JB1 | AMM 24-63-01-400-802 |
| Removal of the Synthetic Vision Computer (SVC) | AMM 34-34-01-000-801 |
| Installation of the Synthetic Vision Computer (SVC) | AMM 34-34-01-400-801 |
| Removal of the Inertial Reference Unit (IRU) | AMM 34-45-01-000-801 |
| Installation of the Inertial Reference Unit (IRU) | AMM 34-45-01-400-801 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Repair Wiring | SPM 20-12-10-02 |
Troubleshooting Recommendations:
If SB100-23-22, SATCOM/FANS installation, is incorporated:
- Reset IRU 1 (CB1-C2) circuit breaker.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap IRUs.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Do wiring check of the ARINC 429 data bus L-IRS-4 between IRU 1 connector A233P1, Junction Box #1, SDU connector A82BP1 and SVC connector A230AP1. Repair/replace as required.
- If system check passes, do close out.
- If fault remains, continue with next step.
NOTE: An internal short of any LRUs connected to this data bus might cause this failure.
- Replace SVC.
- If system check passes, do close out. If fault remains, continue with next step.
- Replace SDU.
- If system check passes, do close out. If fault remains, continue with next step.
- Replace Junction Box #1.
- Do close out.
If SB100-23-22, SATCOM/FANS installation, is not incorporated:
- Reset IRU 1 (CB1-C2) circuit breaker.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap IRUs.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Do wiring check of the ARINC 429 data bus L-IRS-4 between IRU 1 connector A233P1, Junction Box #1 and SVC connector A230AP1. Repair/replace as required.
- If system check passes, do close out.
- If fault remains, continue with next step.
NOTE: An internal short of any LRUs connected to this data bus might cause this failure.
- Replace SVC.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Replace Junction Box #1.
- Do close out.