08/09/21
Message Overview:
Message Description:
The BLEED PRESSURE SENSOR 1 is detected failed. No signal is received or the signal is out of range.
Possible Causes:
- Bleed Pressure Sensor 1 (Left Bleed Pressure Transducer) (MT21)
- Integrated Air System Controller 1 (IASC) (A55)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Operational Test of the Integrated Air System (IAS) Controller | AMM 21-31-01-710-801 |
| Removal of the Bleed Pressure Transducer | AMM 36-11-03-000-801 |
| Installation of the Bleed Pressure Transducer | AMM 36-11-03-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Check the left pressure sensor MT21, interchange or replace Bleed Pressure Transducer.
- Check the wiring between the differential pressure sensor MT21 and the #1 IAS Controller.
- Check the #1 IAS controller circuit breaker CB1 D14 & CB1 E10, reset and re-check MDC for faults.
- Suspect the #1 IAS controller, remove and replace Integrated Air System (IAS) Controller.
- Operational test Integrated Air System (IAS) Controller.