Message Overview:
Message Description:
The Bleed Valve 1 is detected failed in closed position. Check valve or position switch or wiring between the valve and the bleed/air condition panel.
Possible Causes:
- Bleed Valve 1 (Left Intermediate Pressure Valve) (V3)
- Integrated Air System Controller 1 (IASC) (A55)
- Junction Box (JB1)
- Air Conditioning/Bleed Control Panel (Center Pedestal) (PL17)
- Fire-Detection-and-Extinguishing (FIREX) Control-Unit (A91)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Removal of the Junction Box JB1 | AMM 24-63-01-000-802 |
| Installation of the Junction Box JB1 | AMM 24-63-01-400-802 |
| Removal of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-000-801 |
| Installation of the Fire-Detection-and-Extinguishing (FIREX) Control-Unit | AMM 26-11-01-400-801 |
| Operational Test of the Bleed Air System | AMM 36-11-00-710-801 |
| Removal of the Intermediate Pressure Valve | AMM 36-11-05-000-801 |
| Installation of the Intermediate Pressure Valve | AMM 36-11-05-400-801 |
| Removal of the Bleed-Air Control Panel | AMM 36-11-57-000-801 |
| Installation of the Bleed-Air Control Panel | AMM 36-11-57-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Make sure the L BLEED PBA is ON.
- Reset the L BLEED VALVES (V3) circuit breakers CB1-D15.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between the left bleed valve (V3) and the ground. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Manually set the lever of the left bleed valve (V3) to OPEN and CLOSED, then do a continuity check between Pin 4 and Pin 5 of the connector V3J1.
- If there is continuity, go to step 6.
- If there is no continuity, continue with next step.
- Replace the left bleed valve.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do the Operational Test of the Bleed Air System
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between the left bleed valve (V3) and the IASC 1. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swapthe IASC 1 with the IASC 2.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between the left bleed valve and the Air Cond/Bleed Panel. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check of the Air Cond/Bleed Panel. Repair as required or replace the ON/OFF L BLEED PBA.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between the Air Cond/Bleed Panel and the JB1. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between PIN B2 and B3 of the JB1.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace JB 1.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between JB1 and the Circuit Breaker CB1-D15. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between JB1 and the FIREX Control Unit. Repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace the FIREX Control Unit.
- Do Close out.