Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

04/07/21

Message Overview:

Message Name:

NO OUTPUT TO IOC

Message Code:

B3-471475

Associated CAS:

None

Reporting LRU: FSU 2
System Description: 46-00-00
Schematic Diagram: 46-21-00
Wiring Diagram: 46-21-01

Message Description:

ARINC 429 R-File Server Unit (FSU)-1 data bus is reported absent by the Right Input/Output Concentrator (R IOC).

Possible Causes:

  • File Server Unit 2 (FSU 2) (A222)
  • Right Input/Output Concentrator (R IOC) (A4-IOC2)
  • Integrated Avionics Processing System (IAPS) (A4)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

Quick Links:

Operational Test of the Integrated-Avionics Processor System (IAPS) AMM 31-45-00-710-801
Removal of the Integrated-Avionics Processor System (IAPS) Card Cage (ICC) AMM 31-45-01-000-801
Installation of the Integrated-Avionics Processor System (IAPS) Card Cage (ICC) AMM 31-45-01-400-801
Removal of the Input/Output Concentrator Unit (IOC) AMM 31-45-05-000-801
Installation of the Input/Output Concentrator Unit (IOC) AMM 31-45-05-400-801
Operational Test of the Input/Output Concentrator Unit (IOC) AMM 31-45-05-710-801
Removal of the File Server Unit (FSU) AMM 46-21-01-000-801
Installation of the File Server Unit (FSU) AMM 46-21-01-400-801
Wiring - Maintenance Practices - ALL SPM 20-12-00-02
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02
Electrical Connectors - Maintenance Practice - ALL SPM 20-20-00-02

Troubleshooting Recommendations:

  1. Reset R FILE SERVER (CB2-C6) circuit breaker.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  2. Ensure power and grounds are available at FSU 2.

    28 VDC PWR GND Chassis GND
    A222P1-14 A222P1-47 A222P1-35 A222P1-67 A222P1-68

    1. If 28 VDC and grounds are available at FSU 2, go to step 4.
    2. If 28 VDC and/or grounds are not available at FSU 2, continue with next step.

  3. Do wiring check between FSU 2 connector A222P1 and circuit breaker CB2-C6 R FILE SERVER. Replace/repair as required.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  4. Swap IOCs.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  5. Swap FSUs.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  6. Do wiring check of the ARINC 429 R-FSU-1 data bus between FSU 2 connector A222P1 and IAPS connector A4P101. Replace/repair as required.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.
      NOTE: An internal short of any LRU connected to this data bus may cause the fault.

  7. Replace IAPS Card Cage (ICC).
  8. Do close out.