Message Overview:
Message Description:
File Server Unit 2 has reported a External Compensation Unit (ECU) FAULT.
Possible Causes:
- External Compensation Unit (ECU) (A226)
- File Server Unit 2 (FSU 2) (A222)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the File Server Unit (FSU) | AMM 46-21-01-000-801 |
| Installation of the File Server Unit (FSU) | AMM 46-21-01-400-801 |
| Load the Encrypted Application Key (EAK) to the External Compensation Unit (ECU) | AMM 46-21-17-970-801 |
| Removal of the External Compensation Unit - IFIS | AMM 46-21-17-000-801 |
| Installation of the External Compensation Unit - IFIS | AMM 46-21-17-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset R FILE SERVER (CB2-C6) circuit breaker.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between FSU 2 connector A222P1 and ECU 2 connector A226P1. Replace/repair as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap ECUs.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap FSUs.
- Do close out.