Message Overview:
Message Description:
ARINC 429 R-Input/Output Concentrator (IOC)-2 databus is reported inactive by the File Server Unit (FSU) 2 while the right transponder is not reporting it as inactive.
Possible Causes:
- Junction Box (JB2)
- File Server Unit 2 (FSU 2) (A222)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Junction Box JB2 | AMM 24-63-05-000-803 |
| Installation of the Junction Box JB2 | AMM 24-63-05-400-803 |
| Operational Test of Junction Box JB2 Card 2 | AMM 24-63-05-710-827 |
| Removal of the File Server Unit (FSU) | AMM 46-21-01-000-801 |
| Installation of the File Server Unit (FSU) | AMM 46-21-01-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset R FILE SERVER (CB2-C6) circuit breaker.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check of the ARINC 429 data bus R-IOC-2 between Junction Box 2 (Board 5 - TP 13 ARINC Hi / TP 16 ARINC Lo) and FSU 2 connector A222P1. Repair/replace as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap FSUs.
- Do close out.