Message Overview:
Message Description:
The CABIN TEMPERATURE TRIMMER located in the cabin is detected failed.
NOTE: The term "TRIMMER" refers to the Cabin temperature control interface. IASC 1 is connected to a potentiometer controlled via the passenger control Interface. The potentiometer is located inside Ethernet interface Unit 2 (EIU 2). Refer to your supplemental wiring manual for wiring detail.
Possible Causes:
- Integrated Air System Controller 1 (IASC1) (A55)
- Ethernet Interface Unit 2 (EIU2)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Fault Confirmation Procedure:
- Message# = 1
- Fault Logged = AIR,TAXI
- Status = FAILED/WIRING
- Timer = 5
- Logic = IAS1A-55
- {Term Definitions}
- IAS1A-55 XX 353 00 EXCT XXXX-XXXX XXXT-XXXX XXXX-XXXX 353A:21; CABIN TRIM SELECTOR FAIL
Quick Links:
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Swap IASC #1 with IASC #2. Is the fault still present?
- If YES, continue with next step.
- If NO, replace defective IASC and do close out.
- Perform wiring checks between IASC 1 and EIU 2. Refer to your Supplemental wiring manual for interface wiring details.
- If wiring checks are good, continue with next step.
- If defects are found, repair defective wiring as required.
- Swap EIU 2 with EIU 1 for fault confirmation. Replace defective unit if required.
- Do close out.