Message Overview:
Message Description:
Primary or backup mode of control of the TEMPERATURE CONTROL VALVE control has been detected failed in open position.
Possible Causes:
- Temperature Control Valve (MPE07)
- Integrated Air System Controller (IASC1) (A55)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Flight Operation Notifications Manual (FONM): None
NOTES:
- Check for a loose connector on the Temperature Control Valve (MPE07).
Quick Links:
| Removal of the Integrated Air System (IAS) Controller | AMM 21-31-01-000-801 |
| Installation of the Integrated Air System (IAS) Controller | AMM 21-31-01-400-801 |
| Operational Test of the Integrated Air System (IAS) Controller | AMM 21-31-01-710-801 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Repair Wiring | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Do Wiring Check as follows.
From
Temp Control ValveTo
IASC 1Result MPE07P1-4 A55P3-58 MPE07P1-3 A55P3-59 MPE07P1-2 A55P3-64 MPE07P1-1 A55P3-65 MPE07P1-7 A55P1-60 MPE07P1-8 A55P1-73 MPE07P1-13 GS4178 MPE07P1-SH A55P3-SH - Are the results satisfactory?
- If YES, continue with the next step.
- If NO, repair wiring as required and do the close out.
- Interchange the IASC 1 (A55) with IASC 2 (A56).
- Are the results satisfactory?
- If YES, replace the IASC 1 (A55) and do the close out.
- If NO, continue with the next step.
- Replace the Temp Control Valve (MPE07).
- Do the close out.