Message Overview:
Message Description:
No Flap Control Unit (FCU) ARINC Signal at Stall Protection Computer (SPC).
Possible Causes:
- Flap Control Unit (FCU) (A124)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Flap Control Unit (FCU) | AMM 27-51-05-000-801 |
| Installation of the Flap Control Unit (FCU) | AMM 27-51-05-400-801 |
| Operational Test of the Flap Control Unit (FCU) | AMM 27-51-05-710-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset circuit breakers CB1-B13 FLAP L IND, CB1-B14 FLAP CTRL and CB2-B12 FLAP R IND/CTRL.
- If system checks are good, do close out.
- If problem remains, continue to next step.
- Re-rack FCU.
- If system checks are good, do close out.
- If problem remains, continue to next step.
- Do wiring check of M-FCU-1 and M-FCU-2 from FCU to SPC.
- If system checks are good, do close out.
- If problem remains, continue to next step.
- If fault remains, replace FCU.
- Do close out.