Message Overview:
Message Description:
The Flap Control Unit is reporting a failure with the Left Flap Position Sensor.
Possible Causes:
- Left Flap Position Sensor (MPE77)
- Flap Control Unit (FCU) (A124)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-27-0058 - Flap Control Unit - CAS Messages Reset procedure (20501 to 20999)
Forum Articles/Infoservice/Newsletter: None
If Flap Control Unit (FCU) PN: 2257A0000-02 is installed, the reset procedure included in AW300-27-0058 may clear the fault.
Quick Links:
| Removal of the Flap Control Unit (FCU) | AMM 27-51-05-000-801 |
| Installation of the Flap Control Unit (FCU) | AMM 27-51-05-400-801 |
| Operational Test of the Flap Control Unit (FCU) | AMM 27-51-05-710-801 |
| Electrical Rigging of the Flap System | AMM 27-52-00-820-801 |
| Removal of the Flap Position Sensor | AMM 27-52-17-000-802 |
| Installation of the Flap Position Sensor | AMM 27-52-17-400-802 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset the following circuit breakers.
FLAP R IND CB2-B12 FLAP L IND CB1-B13 FLAP CTRL CB1-B14 - Reset the FCU by pressing the FCU reset button on the MAINTENANCE TEST control-panel.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do the Electrical Rigging of the Flap system.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check between FCU connectors A124AP1/ A124BP1 and Left Flap Position Sensor connectors A77AP1/A77BP1. Repair/replace as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Check internal wiring integrity of Left Flap Position Sensor as per the following table.
- If wiring is confirmed good, go to step 7.
- If wiring is found defective, continue with next step.
Channel A Channel B MPE77P1 Value MPE77P2 Value Between pin 1 and pin 2 110Ω Between pin 1 and pin 2 110Ω Between pin 3 and pin 4 75Ω Between pin 3 and pin 4 75Ω Between pin 5 and pin 6 75Ω Between pin 5 and pin 6 75Ω NOTE: A swap of both Flap Position Sensors can also be done to confirm a defective Flap Position Sensor.
- Replace Left Flap Position Sensor.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace FCU.
- Do close out.