Message Overview:
Message Description:
No Mach Number input data from Integrated Standby Instrument.
Possible Causes:
- Junction Box 3 (JB3)
- Integrated Standby Instrument (ISI) (A90)
- Data Concentrator Unit (DCU) (A14)
- Stall Protection Computer (SPC) (A178)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-27-0105 - "STALL PROTECT FAIL" Nuisance CAS Message (20501 - 20999)
- SB100-27-14 - Modification - Stall Protection System - Introduction of the Stall Protection Computer (SPC) Part No. 822-1792-003 to Correct Loopback ARINC 429 Failure Messages (20501 - 20999)
Forum Articles/Infoservice/Newsletter: None
Nuisance CAS message "STALL PROTECT FAIL" (amber) that may be posted at the end of the Stall Protection Computer (SPC) power-up or during the Stall Warning System Pilot Activated Test (PAT). This is the procedure to validate whether there is an actual system fault.
- If the "STALL PROTECT FAIL" message appears after SPC power up, reset the SPC circuit breakers "SPC CH A" (CBP1-B10) and "SPC CH B" (CBP2-B10).
- If the message appears following a PAT, then reset the SPC circuit breakers "SPC CH A" (CBP1-B10) and "SPC CH B" (CBP2-B10). Perform another PAT and make sure the message does not come back.
Quick Links:
| Removal of the Junction Box JB3 | AMM 24-63-09-000-802 |
| Installation of the Junction Box JB3 | AMM 24-63-09-400-802 |
| Functional Test of Junction Box JB3 | AMM 24-63-09-720-801 |
| Operational Test of the Stall Protection System (SPS) | AMM 27-32-00-710-801 |
| Removal of the Stall Protection Computer | AMM 27-32-01-000-801 |
| Installation of the Stall Protection Computer | AMM 27-32-01-400-801 |
| Removal of the Data Concentrator Unit (DCU) | AMM 31-41-01-000-802 |
| Installation of the Data Concentrator Unit (DCU) | AMM 31-41-01-400-802 |
| Removal of the Integrated Standby Instrument | AMM 34-12-01-000-801 |
| Installation of the Integrated Standby Instrument | AMM 34-12-01-400-801 |
| Functional Test of the Integrated Standby Instrument | AMM 34-12-01-720-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset the STBY INST PBA.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Reset the following circuit breakers and perform the Pilot Activated Test (PAT) of the Stall Protection System on the Systems Test control-panel located on the center pedestal.
STALL L PWR CB1-B10 STALL R PWR CB2-B10 - If system checks are good, do close out.
- If fault remains, continue with next step.
- Do wiring check of the ARINC 429 ISI-1 data bus between ISI connector A90P1, Junction Box #3, SPC connectors A178AP1 / A178BP1 and DCU connector A14FP1. Repair/replace as required.
- If system checks are good, do close out.
- If fault remains, continue with next step.
NOTE: An internal short of any LRU connected to this ARINC bus may cause the fault.
- Replace ISI.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace SPC.
- Do close out.