Message Overview:
Message Description:
No R-ADC-6 bus received at SPC channel B.
Possible Causes:
- Right Air Data Computer (ADC 2) (A2)
- Stall Protection Computer (SPC) (A178)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Stall Protection Computer | AMM 27-32-01-000-801 |
| Installation of the Stall Protection Computer | AMM 27-32-01-400-801 |
| Removal of the Air Data Computer | AMM 34-13-01-000-801 |
| Installation of the Air Data Computer | AMM 34-13-01-400-801 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Wire Repair | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset AIR DATA 2 (CB2-C1) circuit breaker.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Do the wiring check of the ARINC 429 databus R-ADC-6 from ADC 2 connector A2P1 to SPC connector A178BP1. Repair/replace as required.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Swap ADCs.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Replace SPC.
- Do close out.