Message Overview:
Message Description:
No data from from Left Input/Output Concentrator (IOC) L-GP-5 bus.
Possible Causes:
- Left Input/Output Concentrator (IOC) (A4-IOC1)
- Flap Control Unit (FCU) (A124)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-27-0058 - Flap Control Unit - CAS Messages Reset procedure (20501 to 20999)
Forum Articles/Infoservice/Newsletter: None
In the MDC system parameters, an FPU PRESS XDCR SIGNAL showing 3740 PSI indicates the FCU have detected a malfunction in the system and have stop sending the excitation signal to the FPU pressure transducer.
MDC REPORT: SYSTEM PARAMETERS
FILENAME:
DATE:
...
FLAP SURFACE ANGLE - 3.74 DEG
FPU PRESS XDCR SIGNAL - 3740 PSI
APU HOURS - 1116.75 HRS
…
Source of the problem still has to be found.
Quick Links:
| Removal of the Flap Control Unit (FCU) | AMM 27-51-05-000-801 |
| Installation of the Flap Control Unit (FCU) | AMM 27-51-05-400-801 |
| Operational Test of the Flap Control Unit (FCU) | AMM 27-51-05-710-801 |
| Removal of the Input/Output Concentrator Unit (IOC) | AMM 31-45-05-000-801 |
| Installation of the Input/Output Concentrator Unit (IOC) | AMM 31-45-05-400-801 |
| Operational Test of the Input/Output Concentrator Unit (IOC) | AMM 31-45-05-710-801 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Reset the following circuit breakers:
- If system checks are good, do close out.
- If fault remains, continue with next step.
FLAP R IND CB2-B12 FLAP L IND CB1-B13 FLAP CTRL CB1-B14 - Reset the FCU by pressing the FCU reset button on the MAINTENANCE TEST control-panel. If unable to reset, engage the Alternate Flaps button with the left hydraulic system pressurized, and attempt another reset using the Flap Reset switch on the left galley.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap the IOCs.
- If fault follow, replace defective IOC. Do system checks and close out.
- If fault remains on left side, continue with next step.
- Check the L-GP-5 bus wiring integrity between L IOC and FCU per AWM.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace FCU per AMM.
- If system checks are good, do close out.