Message Overview:
Message Description:
L-IRS-2 bus data absent at MFD 1 and NOT absent at PFD 1.
Possible Causes:
- Junction Box 1 (JB1)
- Adaptive Flight-Display Unit (MFD) (A29)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Junction Box JB1 | AMM 24-63-01-000-802 |
| Installation of the Junction Box JB1 | AMM 24-63-01-400-802 |
| Removal of the Adaptive Flight-Display Unit | AMM 31-61-01-000-801 |
| Installation of the Adaptive Flight-Display Unit | AMM 31-61-01-400-801 |
| Standard Practices - Replace Wiring | SPM 20-12-00-02 |
| Standard Practices - Repair Wiring | SPM 20-12-10-02 |
Troubleshooting Recommendations:
- Reset L MFD (CB1-C5) and L MFD HTR (CB3-F7) circuit breakers.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Swap AFDs.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Do wiring check of the ARINC 429 data bus L-IRS-2 from MFD 1 connector A29P1 to Junction Box #1. connector JB1AP1 or respective Test Points. Repair/replace as required.
- If system check passes, do close out.
- If fault remains, continue with next step.
- Replace Junction Box #1.
- Do close out.