Message Overview:
Fault Message:
[ACSC2-B] RH PCK IN PRESS XDCR /WRG
Fault Code:
2164415ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-51-00 |
| Schematic Diagram: | 21-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-51-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Right Pack Inlet Pressure Transducer has been detected out of range by Air-Conditioning System Controller (ACSC) 2.
Possible Causes:
- Air-Conditioning System Controller (ACSC) 2 (A88)
- Pack Inlet Pressure Sensor 2 (MT108)
- Junction Box (JB6)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Pack Inlet Pressure-Sensors | AMM 21-51-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Pack Inlet Pressure-Sensors | AMM 21-51-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Junction Box JB6 | AMM 24-00-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Junction Box JB6 | AMM 24-00-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Check CAIMS status of the Pack Inlet Pressure sensor (CAIMS path: SYSTEM DIAG/21-00 AIR CONDITIONING/ACSC 2-B/LRU TEST/R ACSC CH. B PACK TEMP SENSOR DATA).
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Swap Pack Inlet Pressure sensor 2 with Pack Inlet Pressure sensor 1.
- If system checks are good, replace Pack Inlet Pressure sensor 2 and Perform step 1 again.
- If fault remains, continue with next step.
- Swap ACSC 2 with ACSC 1.
- If system checks are good, replace ACSC 2 and Perform step 1 again.
- If fault remains, continue with next step.
- Perform wiring checks between Pack Inlet Pressure sensor and ACSC 2.
- If wiring checks are not good, repair defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Remove JB6 and perform a wiring checks of all wiring / circuit involved with the Pack Inlet Pressure sensors power source.
- If wiring checks are not good, repair defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Perform continuity check of JB6.
- If there is continuity, repair defective associated wiring as required and do close out.
- If there is no continuity, continue with next step.
- Replace JB6.
- Do close out.