Message Overview:
Fault Message:
RF CABLE FROM HGA LNA TO RFU.
Fault Code:
23100D8SC
Associated CAS:
| Reporting LRU: | Satellite Data Unit (SDU) |
| System Description: | 23-13-00 |
| Schematic Diagram: | 23-13-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 23-13-09 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Coax Cable from the High Power Amplifier Low Noise Amplifier (HGA LNA) to the Radio Frequency Unit (RFU) is at fault. For the MCS-7000 installation, the RFU is not external to the Satellite Data Unit (SDU).
Possible Causes:
- Satellite Data Unit (SDU) (A228)
- Radio Frequency Unit (RFU) (A240)
- Diplexer/Low Noise Amplifier (LNA) (A230)
- Coaxial Cable
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
AW 700-23-0584 - Honeywell SDU-600 Obsolescence
AW 700-23-0756 - MCS-7000 Obsolescence
SB 700-23-001 - Modification MCS-6000 SATCOM
SB 700-23-043 - Modification MCS-7000 SATCOM
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Satellite Data Unit | AMM 23-13-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Satellite Data Unit | AMM 23-13-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Diplexer/Low Noise Amplifier | AMM 23-13-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Diplexer/Low Noise Amplifier | AMM 23-13-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Radio Frequency Unit | AMM 23-13-25-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Radio Frequency Unit | AMM 23-13-25-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Disconnect LNA connector A230P2 and RFU connector A240AP1. Perform a continuity check as follows:
From To Result A230P2 center conductor Ground A230P2 center conductor Shield - If there is continuity, repair defective Coax cable as required and do close out.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result A230P2 center conductor A240AP1-71 - If there is continuity, continue with next step.
- If there is no continuity, repair defective Coax cable as required and do close out.
- Replace the LNA. Is the fault still present?
- If YES, continue with next step.
- If NO, do close out.
- Replace the RFU. Is the fault still present?
- If YES, continue with next step.
- If NO, do close out.
- Replace the SDU.
- Do close out.