Message Overview:
Fault Message:
ACPC XFORMER/BRIDGE RECTIFER-T1-CR1
Fault Code:
2451368ACP
Associated CAS:
| Reporting LRU: | AC Power Center (ACPC) |
| System Description: | 24-50-00 |
| Schematic Diagram: | 24-41-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-41-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Fault message is triggered if External AC is AVAIL but there is no 28 V Transformer (T1)/Rectifier (CR1) output detected by the AC-to-DC Converter Card. The output voltage is measured at D4 on Electronic Module (EM) 1 and D8 on EM2.
Possible Causes:
- AC Power Center (ACPC) Contactor (K1)
- Electronic Module (EM1)
- Electronic Module (EM2)
- Electronic Module (EM3)
- Transformer (T1)
- Bridge Rectifier (CR1)
- External AC/DC Converter Card
- AC Power Center (ACPC) (A54)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) External AC-to-DC Converter | AMM 24-51-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) External AC-to-DC Converter | AMM 24-51-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) ZJC-Series Contactor (K1) | AMM 24-51-41-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) ZJC-Series Contactor (K1) | AMM 24-51-41-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) Electronic Modules | AMM 24-51-81-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) Electronic Modules | AMM 24-51-81-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access to System Diagnostics | AMM 45-45-00-970-804 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
| AC Power Center Component Maintenance Manual | CMM 24-51-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Remove Power from the Aircraft.
- Access ACPC primary logic assembly. Disconnect Electric module 3. Perform a continuity check as follows:
From To Result P503-7 Ground P503-8 Ground P503-9 Ground - If there is no continuity, go to step 4.
- If there is continuity, continue with next step.
- Disconnect K1 contacts A3, B3 & C3. Perform a continuity check as follows:
From To Result P503-7 Ground P503-8 Ground P503-9 Ground - If there is continuity, repair defective wiring as required if the short comes from outside the ACPC or replace the ACPC if the short comes from inside the ACPC and do close out.
- If there is no continuity, replace K1 and continue with next step.
- Perform a continuity check as follows:
From To Result P503-7 K1-A3 P503-8 K1-B3 P503-9 K1-C3 - If there is no continuity, go to step 12.
- If there is continuity, continue with next step.
- Perform a continuity check across EM3 as follows:
From To Result J503-7 J503-1 J503-8 J503-2 J503-9 J503-3 - If there is no continuity, replace EM3 and do close out.
- If there is continuity, continue with next step.
- Disconnect EM1 and EM2 connectors (P407 & P206). Perform a continuity check as follows:
From To Result P407-13 Ground P407-14 Ground - If there is continuity, go to step 12.
- If there is no continuity, continue with next step.
- Perform a resistance check on EM1 & EM2 as follows:
From To Ω Result J407-13 J407-4 5.62 KΩ J407-14 J407-4 5.62 KΩ J206-14 J206-4 5.62 KΩ - If the diodes are not serviceable, replace defective EM and do close out.
- If the resistance values are correct, continue with next step.
- Perform a diode check on EM1 & EM2 as follows:
From To Result J407-14 J407-8 J206-14 J206-8 - If the diodes are not serviceable, replace defective EM and do close out.
- If the diodes are serviceable, continue with next step.
- Remove the EXT AC/DC Converter card. Perform a continuity check as follows:
From To Result P407-4 Ground P206-4 Ground - If there is continuity, go to step 12.
- If there is no continuity, continue with next step.
- Perform a continuity check as follows:
From To Result P407-4 P520A-9 P206-4 P520C-30 - If there is continuity, continue with next step.
- If there is no continuity, go to step 12.
- Replace EXT AC/DC Converter card.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Replace ACPC.
- Do close out.