Message Overview:
Fault Message:
FIDEEX CONTROL UNIT FAULT/WRG[PWR]
Fault Code:
261XXXXWK
Associated CAS:
| Reporting LRU: | Fire Detection and Extinguishing (FIDEEX) Control Unit |
| System Description: | 26-11-00 |
| Schematic Diagram: | 26-11-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 26-21-01 [ Global Express ] [ G5000 ] [ Global XRS ] 26-21-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
This message shows when there is an internal failure of Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit or can be linked to Power Supply failure to FIDEEX CU.
Possible Causes:
- Fire Detection and Extinguishing (FIDEEX) Control Unit (A106)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit |
AMM 26-10-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Fire-Detection-and-Extinguishing (FIDEEX) Control-Unit |
AMM 26-10-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Make sure FIDEEX CU circuit breaks are set to in.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Measure for 28 VDC at FIDEEX CU (A106P1) & (A106P2).
- If there is 28 VDC, go to step 6.
- If no 28 VDC, continue with next step.
- Perform wiring checks between SPADA No. 2 (A14P1) and FIDEEX CU (A106P1).
- If the wiring checks are not good, replace the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Perform wiring checks between SPADA No. 3 (A15P1) and FIDEEX CU (A106P2).
- If the wiring checks are not good, replace the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Perform wiring checks between DCPC (A63P3)/(A63P4) and FIDEEX CU (A106P1)/(A106P2).
- If the wiring checks are not good, replace the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Replace FIDEEX CU.
- Do close out.