Require immediate crew attention. These messages are accompanied by flashing master warning, triple chime attenson with or without voice message or dedicated tone. Require immediate crew awareness and future crew action may be required in the form of alternate system selection or performance limitation. These message are accompanied by flashing master caution and a single chime. Indicate safe or normal system operation which require crew awareness, over and above the dark cockpit philosophy. Indicate minor failures or reduction in systems capability, which require no crew action.

This page includes :

For AOG assistance contact:

CRC Montreal (YUL)
Quick Links

07/03/19

Message Overview:

Fault Message:

SLAT RESOLVER EXCITATION/SFCU#2/WRG

Fault Code:

2752258STD

Associated CAS:

None

Reporting LRU: Slat/Flap Control Unit (SFCU) 2
System Description: 27-53-00
Schematic Diagram: 27-50-00 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wiring Diagram: 27-50-05 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Fault Description:

When one of the following conditions occurs:

  • The output voltage is not within the permitted range
  • The output current is not within the permitted range

Possible Causes:

  • Slat Flap Control Unit (SFCU) 2 (A95)
  • Right Slat Resolver (MT78)
  • Left Slat Resolver (MT77)
  • Associated Wiring

Troubleshooting Tips:

Advisory Wire/Service Bulletin: None

Forum Articles/Infoservice/Newsletter: None

Quick Links:

Removal of the Slat/Flap Control Unit (SFCU) AMM 27-51-05-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Slat/Flap Control Unit (SFCU) AMM 27-51-05-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Removal of the Slat Resolvers AMM 27-53-41-000-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Installation of the Slat Resolvers AMM 27-53-41-400-801 [ Global Express ]  [ G5000 ]  [ Global XRS ]
Wire Repair - Maintenance Practices - ALL SPM 20-12-10-02 [ Global Express ]  [ G5000 ]  [ Global XRS ]

Troubleshooting Recommendations:

  1. On the EMS CDU, select CTRL function and SLAT/FLAP RESET.
    NOTE: Wait at least one minute after SFCU reset to allow self-test to run.

    1. If system checks are good, do close out.
    2. If fault remains, continue with next step.

  2. Swap SFCU 2 with SFCU 1.

    1. If system checks are good, replace SFCU 2 and do close out.
    2. If fault remains, continue with next step.

  3. Check resistance value as follows:
    NOTE: Performing this resistance check will verify the interface wiring in addition to the resolver.

    Source From To Expected Result Result
    from Left Slat Resolver A95AP1-2 A95AP1-1 166 to 170 ohms
    from Right Slat Resolver A95AP1-14 A95AP1-13 166 to 170 ohms

    1. If resistance checks are out of tolerance, repair defective wiring as required and do close out.
    2. If resistance checks are within tolerance, continue with next step.

  4. Perform a resistance check of the resolver as follows:

    Source From To Expected Result Result
    Left Slat Resolver MT77J1-8 MT77J1-7 166 to 170 ohms
    Right Slat Resolver MT78J1-8 MT78J1-7 166 to 170 ohms

    1. If resistance checks are out of tolerance, go to step 6.
    2. If resistance of the resolver is within tolerance, continue with next step.

  5. Perform wiring checks between the applicable SFCU and resolver.

    1. If wiring checks are not good, repair defective wiring as required and do close out.
    2. If wiring checks are good, continue with next step.

  6. Replace resolver.
  7. Do close out.