09/12/19
Message Overview:
Fault Message:
BMC2 DISCRETE INPUT WIRING
Fault Code:
3616422BMC
Associated CAS:
| Reporting LRU: | Bleed Management Controller (BMC) 2 |
| System Description: | 36-11-00 |
| Schematic Diagram: | 36-11-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 36-11-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
Bleed Management Controller (BMC) 2 Power-up Built-In Test (PBIT) cannot read pin programming properly.
Possible Causes:
- Bleed Management Controller (BMC) 2 (A70)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Bleed Management Controller | AMM 36-11-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Bleed Management Controller | AMM 36-11-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Perform wiring checks between BMC 2 and ground as follows:
From To Result A70P2-37 Ground - If wiring checks are not good, repair defective wiring as required and do close out.
- If wiring checks are good, continue with next step.
- Replace BMC 2.
- Do close out.