Message Overview:
Message Name:
AIRFLOW INTO PASSENGER COMPARTMENT HIGHER THAN VALUE SET WITH R PACK CONTROL ROTARY SWITCH
| Identifier: | 215OBS005 |
| Effectivity: | All |
| System: | Air Conditioning |
| Associated CAS: | None |
| System Description | 21-51-00 |
| Schematic Diagram: | 21-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-51-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
The total airflow which goes into the passenger compartment is apparently higher than the set value on the PACK CONTROL rotary switch on the BLEED AIR control panel.
Possible Causes:
- Pack Inlet Pressure Sensor has low drift
- Leakage at the Pneumatic Line Location between the Flow Sensor Venturi and the Pack Inlet Pressure Sensor
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Notice To Operators (NTO): None
Flight Operation Notifications Manual (FONM): None
Quick Links:
| Flow Sensor Venturis - Removal | AMM 21-51-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Flow Sensor Venturis - Installation | AMM 21-51-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Pack Inlet Pressure Sensor - Removal | AMM 21-51-17-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Pack Inlet Pressure Sensor - Installation | AMM 21-51-17-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Access System Diagnostics | AMM 45-45-00-970-804 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair | SPM 20-12-10 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Do a leak test at the pneumatic line location between the right flow sensor venturi and the right pack inlet pressure sensor as follows:
- Examine the pneumatic line and pneumatic line connections.
- Use the leak detector to find leaks and make a mark on the location where leaks are found.
- If there is a leak in the pneumatic line, repair the leak.
- Interchange flow sensor venturis.
- If system checks are good, do close out.
- If fault remains, continue with next step.
- Interchange Pack Inlet Pressure Sensors.
- Do close out.