02/25/21
Message Overview:
Message Description:
The Left Generator Sensor has detected a current imbalance between the 2 feeders.
A failure with the Left Generator Sensor or Left Protection PCB has been reported by the Left DCPC.
Possible Causes:
- Left Generator power feeders terminal lugs corroded / Oxidized and / or under torqued at left generator or left DCPC
- Left Generator Sensor (DPMS1 or MPE071)
- Left DC Power-Center Protection (LPROT) (PCB1)
- Left Generator Power Feeders
- Left DC Power Center (LDCPC) (A35)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW300-24-0024 - Electrical System - Troubleshooting Tips:
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Main Generator | AMM 24-31-05-000-801 |
| Installation of the Main Generator | AMM 24-31-05-400-801 |
| Removal of the DC Power Center (DCPC) | AMM 24-61-01-000-801 |
| Installation of the DC Power Center (DCPC) | AMM 24-61-01-400-801 |
| Removal of the Generator Sensor | AMM 24-61-41-000-801 |
| Installation of the Generator Sensor | AMM 24-61-41-400-801 |
| Removal of the DC Power-Center Protection | AMM 24-61-77-000-801 |
| Installation of the DC Power-Center Protection | AMM 24-61-77-400-801 |
| Generator Load test Procedure | RIL BD-0069 |
| Wiring - Maintenance Practices - ALL | SPM 20-12-00-02 |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 |
| Electrical Connectors - Maintenance Practice - ALL | SPM 20-20-00-02 |
Troubleshooting Recommendations:
- Do visual inspection of the feeder cables between the left Generator G1 positive terminal block and the left DC Power-Center T11 and T12 Studs.
- If inspection is satisfying, continue with next step.
- If inspection and wiring check are not satisfying, repair/replace defective wiring.
- Make sure the left Generator power feeder cables terminal lugs are free of any corrosion / oxidation at left DC Power-Center T11 and T12 Studs and left generator positive terminal stud.
- If inspection is satisfying, continue with next step.
- If inspection is not satisfying, clean affected terminal lugs as per best shop practices.
- Make sure the left generator positive stud hardware stack up is installed and torqued as per AMM's generator installation task 24-31-05-400-801.
- If inspection is satisfying, continue with next step.
- If inspection is not satisfying, reinstall the left generator positive terminal stud hardware stack up as per AMM's generator installation task
- Make sure the left DC Power-Center terminal studs T11 and T12 hardware is installed and torqued as per AMM TASK 24-61-77-400-801
- If inspection is satisfying, continue with next step.
- If inspection is not satisfying, torque the left DC Power-Center studs T11 and T12 hardware as per specs.
NOTE: At the operator's discretion, a Generator Load Test can be performed to ensure the generator functionality under heavy output load. Refer to RIL BD-0069.
- Disconnect the left Generator Sensor (DPMS1) connector. Do visual inspection of the connector and associated wiring for any loose pins and/or damaged wire.
- If inspection is satisfying, continue with next step.
- If inspection is not satisfying, go to step 5.
- Swap the left Generator Sensor (DPMS1) with the Right Generator Sensor (DPMS2). Is the fault message still present?
- If YES, continue with next step.
- If NO, replace the defective Generator Sensor.
- Swap the left DC Power-Center Protection (PCB1) with the right Power-Center Protection (PCB2). Is the fault message still present?
- If YES, continue with next step.
- If NO, replace the defective DC Power-Center Protection.
- Replace the left DC Power-Center (A35).
- Do close out.