09/11/23
Message Overview:
Fault Message:
CPC1 DISCRETE INPUT WIRING
Fault Code:
2137325ABG
Associated CAS:
| Reporting LRU: | Cabin Pressure Controller (CPC) 1 |
| System Description: | 21-31-00 - Cabin-Pressure Control |
| Schematic Diagram: | [ Global Express ] [ G5000 ] [ Global XRS ] 21-31-00-101 - Cabin Pressure Control System |
| Wiring Diagram: | [ Global Express ] [ G5000 ] [ Global XRS ] 21-31-01-1 - Cabin Pressure Control System # 1 |
Message Description:
Cabin Pressure Controller (CPC) 1 does not recognize the pin programming.
Possible Causes:
- Cabin Pressure Controller (CPC) 1 (A21)
- Ground Stud (GS135)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Standard Aircraft Configuration for Maintenance | [ G5000 ] [ Global Express ] [ Global XRS ] AMM12-00-00-867-801 |
| Aircraft Walkaround (for Maintenance) | [ G5000 ] [ Global Express ] [ Global XRS ] AMM12-00-00-867-802 |
| Removal of the Cabin Pressure Controllers | [ G5000 ] [ Global Express ] [ Global XRS ] AMM21-31-01-000-801 |
| Installation of the Cabin Pressure Controllers | [ G5000 ] [ Global Express ] [ Global XRS ] AMM21-31-01-400-801 |
| Operational Test of the Cabin-Pressure-Controller Pressure Sensors | [ G5000 ] [ Global Express ] [ Global XRS ] AMM21-31-01-710-801 |
| Connect Electrical Power to the Aircraft | [ G5000 ] [ Global Express ] [ Global XRS ] AMM24-00-00-861-801 |
| Electrical/Electronic Safety Precautions | [ G5000 ] [ Global Express ] [ Global XRS ] AMM24-00-00-910-801 |
| Electrostatic Discharge Safety Precautions | [ G5000 ] [ Global Express ] [ Global XRS ] AMM24-00-00-910-802 |
| CAIMS PMAT General Instructions | [ G5000 ] [ Global Express ] [ Global XRS ] AMM45-45-00-970-801 |
| Access to Active Faults | [ G5000 ] [ Global Express ] [ Global XRS ] AMM45-45-00-970-802 |
| Access to Stored Faults | [ G5000 ] [ Global Express ] [ Global XRS ] AMM45-45-00-970-803 |
| Access to System Diagnostics | [ G5000 ] [ Global Express ] [ Global XRS ] AMM45-45-00-970-804 |
Troubleshooting Recommendations:
- Perform wiring checks of the wire connected to A21P1-13.
- If the wiring checks are good, go to step 4.
- If the wiring checks are not good, repair as required and do the close out.
- Make sure GS135 is properly grounded.
- If GS135 is not properly grounded, repair as required and do close out.
- If GS135 is properly grounded, continue with the next step.
- Perform visual check of A21P1-12. Make sure there is no wire connected to pin 12. Pin 12 is used for CPC 2 position.
- If fault indication is gone, do close out.
- If fault remains, continue with the next step.
- Interchange CPC 1 with CPC 2.
- Does the fault follow the CPC?
- If YES, replace the CPC 1 and do close out.
- If NO, continue with the next step.
- Do close out.