Message Overview:
Message Name:
[ACSC1-A] LH TEMP CONT VLV CMD /TCV
Message Code:
2161320ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 1 |
| System Description: | 21-60-00 - Temperature Control |
| Schematic Diagram: | 21-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-52-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
The Temperature Control Valve #1 position does not agree with the Air Conditioning System Controller (ACSC) 1 command.
Possible Causes:
- Left Temperature Control Valve (L23)
- Left Air Conditioning System Controller (ACSC) (A87)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Full Throttle Blog/Forum Articles/Infoservice/Newsletter: None
Flight Operation Notifications Manual (FONM): None
NOTES:
- Ensure the ACM is running efficiently and has no air leaks.
Quick Links:
| Removal of the Temperature Control Valves | AMM 21-52-33-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Temperature Control Valves | AMM 21-52-33-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Interchange left Temperature Control Valve with right Temperature Control Valve.
- If system checks are good, replace left Temperature Control Valve and do close out.
- If fault remains, continue with next step.
- Interchange ACSCs.
- If system checks are good, replace the defective ACSC and do close out.
- If fault remains, continue with next step.
- Perform wiring checks between the Temperature Control Valve and ACSC 1.
- Repair defective wiring and do close out.