06/10/19
Message Overview:
Fault Message:
ACSC1 [CH B NO DATA] /DAU3 [A] /WRG
Fault Code:
2162326ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 1 |
| System Description: | 21-60-00 |
| Schematic Diagram: | 21-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-51-01 [ Global Express ] [ G5000 ] [ Global XRS ] 31-42-07 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Air Conditioning System Controller (ACSC) 1 Channel B does not receive data from Data Acquisition Unit (DAU) 3.
Possible Causes:
- Data Acquisition Units (DAU) 3 (A30)
- Air Conditioning System Controller (ACSC) 1 (A87)
- Junction Box (JB3)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active (Global Express / XRS - (9002 to 9312, 9314 to 9380, 9384 to 9429) and Global 5000 - (9127 to 9383, 9389 to 9400, 9404 to 9431 and 9998))
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Junction Box JB3 | AMM 24-00-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Junction Box JB3 | AMM 24-00-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap DAU 3 with DAU 4.
- If system checks are good, replace DAU#3 and do close out.
- If fault remains, continue with next step.
- Swap ACSC 1 with ACSC 2.
- If system checks are good, replace ACSC 1 and do close out.
- If fault remains, continue with next step.
- Perform wiring checks between ACSC 1, DAU#3 and JB3 (ref: Wiring Manual: 31-42-00 Sheet 7 of 9, page 1).
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Replace JB3.
- Do close out.