Message Overview:
Fault Message:
[ACSC1-B] TMP PNL AFT SELECTOR /WRG
Fault Code:
2162526ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 1 |
| System Description: | 21-60-00 |
| Schematic Diagram: | 21-60-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-60-03 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
The Aft Cabin Temperature Selector (located on the Bleed-Air Control Panel) has been detected out of range by the Left Air Conditioning Controller (ACSC).
Possible Causes:
- Air Conditioning System Controller 1 (A87)
- Aft Cabin Temperature Selector (R1)
- Bleed Air Control Panel (AP8)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the BLEED-AIR Control Panel | AMM 36-11-57-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the BLEED-AIR Control Panel | AMM 36-11-57-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Perform wiring checks between ACSC 1 and the AFT temperature SELECTOR located on the BLEED-AIR Control Panel.
- If wiring checks are not good, repair the defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Perform wiring checks of the BLEED-AIR Control Panel.
- If wiring checks are not good, repair the defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Measure AFT temperature potentiometer (R1) total resistance. Resistance should be 1000 ohms.
- Connect the Ohm meter on the potentiometer wiper. Rotate potentiometer slowly and make sure there is no dead spot on potentiometer or any other deficiencies.
- Replace ACSC 1.
- Do close out.