11/21/23
Message Overview:
Message Name:
[ACSC2-A] RH TEMP CONT VLV CMD /TCV
Message Code:
2163320ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-52-00 |
| Schematic Diagram: | 21-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-52-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Message Description:
The Temperature Control Valve #2 position does not agree with the Air Conditioning System Controller (ACSC) 2 command.
Possible Causes:
- Right Temperature Control Valve (TCV) (L29)
- Air Conditioning System Controller (ACSC) 2 (A88)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Standard Aircraft Configuration for Maintenance | AMM12-00-00-867-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Aircraft Walkaround (for Maintenance) | AMM12-00-00-867-802 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Removal of the Temperature Control Valves | AMM21-52-33-000-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Installation of the Temperature Control Valves | AMM21-52-33-400-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM21-60-21-000-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM21-60-21-400-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Connect Electrical Power to the Aircraft | AMM24-00-00-861-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Electrical/Electronic Safety Precautions | AMM24-00-00-910-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Electrostatic Discharge Safety Precautions | AMM24-00-00-910-802 [ G5000 ] [ Global Express ] [ Global XRS ] |
| CAIMS PMAT General Instructions | AMM45-45-00-970-801 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Access to Active Faults | AMM45-45-00-970-802 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Access to Stored Faults | AMM45-45-00-970-803 [ G5000 ] [ Global Express ] [ Global XRS ] |
| Access to System Diagnostics | AMM45-45-00-970-804 [ G5000 ] [ Global Express ] [ Global XRS ] |
Troubleshooting Recommendations:
- Check the status of the temp control valve command in CAIMS (CAIMS path SYSTEM DIAG/21-00 AIR CONDITIONING/ACSC-2B/LRU TEST/R ACSC CH.B CNTL PNL & VALVE DATA).
- Perform a wiring check of all wires between the Temperature Control Valve and ACSC 2.
- If wiring checks are not good, repair the defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Interchange Temperature Control Valve 2 with Temperature Control Valve 1.
- If the system check is good, replace Temperature Control Valve 2 and do close out.
- If the fault remains, continue with next step.
- Replace ACSC 2.
- Do close out.