Message Overview:
Fault Message:
[ACSC2-A] RH PCK DIS TEMP SENS /WRG
Fault Code:
2163422ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-52-00 |
| Schematic Diagram: | 21-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-52-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Right Pack Discharge Temperature-Sensors has been detected out of range by Air Conditioning System Controller (ACSC) 2 Channel A.
Possible Causes:
- Pack Discharge Temperature Sensor (PDTS) 2 (E33)
- Data Acquisition Unit (DAU) 2 (A18)
- Air Conditioning System Controller (ACSC) 2 (A88)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active (Global Express / XRS - 9002 to 9312, 9314 to 9380, 9384 to 9429 and Global 5000 - 9127 to 9383, 9389 to 9400, 9404 to 9431 and 9998)
- AW700-45-0065 - CAIMS Nuisance Fault Messages (Global Express - 9002 to 9153 and Global 5000 - 9127 to 9411, 9417 to 9431, 9998 and Global Express XRS - 9159 to 9429)
Forum Articles/Infoservice/Newsletter: None
Quick Links:
| Removal of the Pack Discharge Temperature-Sensors | AMM 21-52-37-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Pack Discharge Temperature-Sensors | AMM 21-52-37-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Data Acquisition Units (DAU) | AMM 31-42-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Data Acquisition Units (DAU) | AMM 31-42-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap Pack Discharge Temperature Sensor 2 with Pack Discharge Temperature Sensor 1. Is the fault still present?
- If NO, replace Pack Discharge Temperature Sensor 2 and do close out.
- If YES, continue with next step.
- Perform wiring checks between Pack Discharge Temperature Sensor and ACSC 2.
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Perform wiring checks between Pack Discharge Temperature Sensor and DAU 2.
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Swap DAU 2 with DAU 1. Is the fault still present?
- If NO, replace DAU 2 and do close out.
- If YES, continue with next step.
- Replace ACSC 2.
- Do close out.