Message Overview:
Fault Message:
[ACSC2-A] RH MIX-MANI TEMP SENS/WRG
Fault Code:
2163426ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-20-00 |
| Schematic Diagram: | 21-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-21-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Right Mix Manifold Temperature-Sensor has been detected out of range by Air Conditioning System Controller (ACSC) 2 Channel A.
Possible Causes:
- Mix Manifold Temperature Sensor 2 (E30)
- Air Conditioning System Controller (ACSC) 2 (A88)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active (Global Express / XRS - 9002 to 9312, 9314 to 9380, 9384 to 9429 and Global 5000 - 9127 to 9383, 9389 to 9400, 9404 to 9431 and 9998)
Forum Articles/Infoservice/Newsletter: None
CAIMS has Pack Temp. Sensor Data for ACSC controllers on all 4 channels. This will show sensor data and give you an idea of problem areas, even with the air system not operating, but power is on.
Quick Links:
| Removal of the Mix Manifold Temperature-Sensors | AMM 21-21-09-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Mix Manifold Temperature-Sensors | AMM 21-21-09-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Swap Mix Manifold Temperature-Sensor 2 with Mix Manifold Temperature-Sensor 1.
- If system checks are good, replace Mix Manifold Temperature-Sensor 2 and do close out.
- If fault remains, continue with next step.
- Perform wiring checks between Mix Manifold Temperature-Sensor and ACSC 2.
- If the wiring checks are not good, repair the defective associated wiring and do close out.
- If the wiring checks are good, continue with next step.
- Replace ACSC 2.
- Do close out.