06/12/19
Message Overview:
Fault Message:
[ACSC2-B] RH A-I PRESS XDCR/WRG
Fault Code:
2164416ECS
Associated CAS:
| Reporting LRU: | Air Conditioning System Controller (ACSC) 2 |
| System Description: | 21-52-00 |
| Schematic Diagram: | 21-52-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 21-52-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Right Pack Anti-Ice Pressure Sensors has been detected out of range by Air-Conditioning System Controller (ACSC) 2 Channel B.
Possible Causes:
- Anti-Icing Pressure Sensor 2 (MT107)
- Air-Conditioning System Controller (ACSC) 2 (A88)
- Junction Box (JB6)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin:
- AW700-21-0160 - "PACK FAULT" CAS message while CAIMS / OMS is active
Forum Articles/Infoservice/Newsletter: None
CAIMS has Pack Pressure XDCR. Data for ACSC controllers on all 4 channels. This will show sensor data and give you an idea of problem areas.
If CAIMS messages [ACSC2-A] RH PCK IN FLOW SENS/WRG, [ACSC2-A] RH PCK IN PRESS XDCR/WRG,[ACSC2-B] RH PCK IN FLOW SENS/WRG, and [ACSC2-A] RH PCK IN PRESS XDCR/WRG all shown, most possible cause is the SPDA No.4 failure.
Quick Links:
| Removal of the Anti-Icing Pressure Sensors | AMM 21-52-41-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Anti-Icing Pressure Sensors | AMM 21-52-41-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Air-Conditioning System Controllers | AMM 21-60-21-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Air-Conditioning System Controllers | AMM 21-60-21-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Junction Box JB6 | AMM 24-00-13-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Junction Box JB6 | AMM 24-00-13-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- Check CAIMS status of the Pack Anti-Ice Pressure Sensors (SYSTEM DIAG/21-00 AIR CONDITIONING/ACSC 2-B/LRU TEST/R ACSC CH. B PACK PRESSURE SENSOR DATA).
- Swap Pack Anti-Ice Pressure Sensor 2 with Pack Anti-Ice Pressure Sensor 1.
- If system checks are good, replace Pack Anti-Ice Pressure Sensor 2 and do close out.
- If fault remains, continue with next step.
- Perform a wiring check between RH Pack Anti-Ice Pressure Sensor, JB6, ACSC 2 and Gnd.
- If wiring checks are not good, repair defective associated wiring and do close out.
- If wiring checks are good, continue with next step.
- Swap ACSC 2 with ACSC 1.
- If system checks are good, replace ACSC 2 and do close out.
- If fault remains, continue with next step.
- Replace JB6.
- Do close out.