Message Overview:
Fault Message:
APU GEN [PHASE NEUTRAL CROSSED]
Fault Code:
2420109LPS
Associated CAS:
| Reporting LRU: | Auxiliary Power Unit (APU) Generator |
| System Description: | 24-22-00 |
| Schematic Diagram: | 24-22-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-22-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
Auxiliary Power Unit (APU) Generator has tripped off-line or will not come on-line.
Possible Causes:
- Ground Stud (GS678)
- Auxiliary Power Unit (APU) Generator Control Unit (GCU) (A109)
- Auxiliary Power Unit (APU) Generator (A110)
- Associated Wiring
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter:
NOTE: The Generator ground stud connection may need to be visually inspected for signs of arcing.
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCU 1, GCU 2, GCU 3, GCU 4 and the APU GCU into a different position (for troubleshooting only). You can monitor the GCU faults in CAIMS via the active fault page.
Quick Links:
| Removal of the APU Generator | AMM 24-22-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the APU Generator | AMM 24-22-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the AC Power Center (ACPC) | AMM 24-51-00-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the AC Power Center (ACPC) | AMM 24-51-00-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Electrical Bonding - Adjustment/Test | SPM 51-80-00-05 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wire Repair - Maintenance Practices - ALL | SPM 20-12-10-02 [ Global Express ] [ G5000 ] [ Global XRS ] |
Troubleshooting Recommendations:
- At the APU Generator, do a check of the output connections at the terminal block. Are the connections as shown in the table below?
Connection Color T1 White T2 Blue T3 Orange G Green - If NO, reconnect or repair as required and do close out.
- If YES, continue with next step.
- At the ACPC, do a check of the APU Generator output connection at the APU 5 LCTA. Are the connections as shown in the table below?
Connection Color T13 White T14 Blue T15 Orange - If NO, reconnect or repair as required and do close out.
- If YES, continue with next step.
- Perform a bonding test of ground stud GS678.
From To Expected result Result GS678 Ground <0.010 ohms - If the resistance value is higher than 0.010 ohms, repair ground stud and do close out.
- If the resistance value is good, continue with next step.
- Swap APU GCU with GCU #2 (physically or using the GCU patch cable). Is the fault still present?
- If NO, replace APU GCU and do close out.
- If YES, continue with next step.
- Replace APU Generator.
- Do close out.