06/25/19
Message Overview:
Fault Message:
GEN1 OVERFREQUENCY FAULT
Fault Code:
2421112LPS
Associated CAS:
| Reporting LRU: | Generator Control Unit (GCU) 1 |
| System Description: | 21-21-00 |
| Schematic Diagram: | 24-21-00 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Wiring Diagram: | 24-21-01 [ Global Express ] [ G5000 ] [ Global XRS ] |
Fault Description:
An over-frequency failure signal is given when the line frequency of the Variable Frequency Generator (VFG) (PMG frequency) is more than 629 ±1 Hz.
Possible Causes:
- Generator Control Unit (GCU) 1 (A56)
- Variable Frequency Generator (VFG) 1 (G1)
Troubleshooting Tips:
Advisory Wire/Service Bulletin: None
Forum Articles/Infoservice/Newsletter: None
A GCU patch cable (GSE REF # 24X-24-02) can be used to swap GCUs 1, 4 and 5 into position 2 or 3 (for troubleshooting only)The GCU NVMs can only be downloaded at position #2 or #3
NOTE:
- When generator is switched off, two reset attempts can be made. If NOT successful, reset will only be possible with a complete power cycle.
- The frequency necessary to reset must be at least 5Hz less than the frequency which caused the failure.
Quick Links:
| Removal of the Variable Frequency Generators (VFG) | AMM 24-21-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Variable Frequency Generators (VFG) | AMM 24-21-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Removal of the Generator Control Units (GCU) | AMM 24-24-01-000-801 [ Global Express ] [ G5000 ] [ Global XRS ] |
| Installation of the Generator Control Units (GCU) | AMM 24-24-01-400-801 [ Global Express ] [ G5000 ] [ Global XRS ] |